The warning-label sheet identifies the markings required for the project. Depending on the plan set, it may show:
A standard NEC solar placard set is included with each system which covers most common requirements. However, no generic label kit can account for every code edition, utility rule, AHJ requirement, system configuration, or project-specific value. Compare the supplied set with the approved warning-label sheet before installation.
A building with solar or energy storage may remain energized from more than one source. Turning off the utility service does not necessarily de-energize PV source circuits, inverter inputs, batteries, or backup equipment.
Labels help identify:
Labels communicate hazards and operating information; they do not make equipment safe to touch. Qualified persons must still follow the applicable shutdown, verification, lockout, and electrical-safety procedures.
Begin by reviewing every label shown on the approved plan sheet. For each item, identify:
Create a label schedule or mark off each item directly on a working copy of the sheet. Do not assume that a package labeled “solar placard set” contains every marking required for the project.
The applicable requirements depend on the adopted code edition and local amendments. A label intended for one NEC edition or system type may not be correct for another.
Equipment labels are installed on or adjacent to specific electrical components, such as:
These labels may identify the equipment’s purpose, operating ratings, power sources, shutdown procedure, or electrical hazard.
Do not place a label directly on utility-owned equipment unless the utility permits that location. Follow the approved plan and utility requirements for markings at the meter or service.
These labels identify wiring associated with PV, storage, or other power sources. They may be required on:
The approved plans or applicable requirements may specify the wording, color, reflectivity, spacing, and locations.
Do not apply a single raceway label and assume the entire route is covered. Markings may be required repeatedly and at penetrations, turns, enclosures, or other defined points. Use the spacing and placement rules applicable to the project’s adopted code and approved design.
A directory or site placard helps responders and service personnel locate equipment that is not grouped together or immediately visible.
It may show:
The placard should agree with the approved site plan and actual installed conditions. If equipment is relocated through an approved field revision, update the directory or map before inspection.
A generic warning sticker cannot replace a required site-specific directory.
Not every installed label must necessarily reproduce the plan-sheet artwork pixel for pixel. Font family, border thickness, or line breaks may differ while still satisfying the applicable requirement.
However, “same general idea” is not enough by itself. Confirm that the installed label preserves all required elements, including:
Some code provisions allow wording that is substantially equivalent; others prescribe particular language or content. Do not paraphrase required safety language without confirming that the alternative is acceptable to the designer and AHJ.
Some labels contain values taken from the single-line diagram or equipment calculations, including:
Copy these values from the current approved plans—not from a sales proposal, preliminary estimate, equipment advertisement, or prior revision.
Check units as carefully as the numbers. Do not confuse:
When write-in labels are used, complete them neatly with a permanent marking method suitable for the label material and environment.
The rapid-shutdown marking helps emergency responders identify:
The placard graphic and wording must match the actual system architecture. A marking for a system that reduces voltage at the module level may not be appropriate for a system with different controlled limits or boundaries.
Install the initiation-device label at the actual switch or disconnect used to initiate rapid shutdown. Do not place it on a nearby device that does not perform that function.
After installation, verify the relationship among:
Service equipment and distribution panels may be energized from the utility, PV system, battery, generator, or another source.
Multiple-source warnings should accurately identify the sources connected to the equipment. A dual-power-source label may be insufficient when three or more sources are present.
If disconnects are not grouped, a directory may also be required to identify their locations. Update existing directories and panel schedules when the project changes the building’s power-source configuration.
Each disconnect should be clearly associated with the equipment or circuit it controls.
The label may need to identify:
Do not label a device simply “solar disconnect” if the approved plans distinguish between AC, DC, battery, rapid-shutdown, or utility-operational functions.
Confirm that the label remains visible when the equipment is installed and that it cannot easily be mistaken for the label of an adjacent device.
At service equipment, panelboards, or generation panels, markings may identify:
Install breaker identifiers where they remain associated with the correct breaker. A label placed loosely inside a panel directory or on a removable dead front can become misleading if equipment is rearranged.
Do not cover manufacturer nameplates, breaker ratings, circuit directories, ventilation openings, fasteners, or required operating instructions.
A durable adhesive label set can satisfy many standard equipment and raceway-marking requirements when the labels are suitable for their environment and installed correctly.
A custom engraved, metal, or permanently printed placard is commonly needed when:
Use materials suitable for the installation environment. Outdoor labels and placards may be exposed to ultraviolet light, moisture, heat, cold, cleaning chemicals, and abrasion.
“Listed” and “weather resistant” are not interchangeable descriptions. Confirm the material, adhesive, substrate, and printing method required for the particular application.
Custom site placards and additional labels can be sourced from PV Labels.
Before ordering, prepare the following:
For a site map, also provide:
Review the proof carefully. Verify spelling, equipment names, map orientation, electrical values, colors, and quantities before approving production.
Order custom placards after the approved warning-label sheet and final electrical design are available, but early enough to receive and inspect them before the required inspection.
Permit corrections, utility review comments, equipment substitutions, and design revisions can change:
Avoid ordering project-specific placards from a preliminary plan unless the possibility and cost of replacement are understood.
If the design changes after ordering, compare every custom placard with the revised plans. Do not install an obsolete placard merely because it has already been purchased.
Labels perform properly only when installed on suitable surfaces.
Before application:
Do not apply adhesive labels to wet, dirty, corroded, heavily textured, or deteriorated surfaces and expect them to remain legible.
Avoid placing labels on removable covers when doing so could separate the marking from the equipment or create confusion after servicing. Follow the approved placement detail and AHJ requirements.
After all equipment is installed, walk the system in the same order used to read the single-line diagram:
At each point, compare the installed label with the approved label sheet and actual equipment.
Then stand at the normal emergency-response or utility approach location. Confirm that required directories, disconnect markings, and shutdown instructions are visible, accurate, and understandable.
Common errors include:
Labels and placards are part of the installed safety system, not inspection-day decoration. They must remain accurate, visible, legible, and associated with the correct equipment.
If the supplied label set differs from the approved label sheet, determine whether the proposed wording and format satisfy the applicable requirement. When uncertain, obtain clarification from the designer or AHJ before installation.