Enphase IQ Meter Collar: Meter Socket and Installation Requirements

Enphase IQ Meter Collar: Meter Socket and Installation Requirements

Overview-

The Enphase IQ Meter Collar is designed for use with a standard ANSI C12 Form 2S meter socket rated for 200 A continuous service.

The collar may be installed in either of the following locations:

• Behind the utility meter
• In a separate load-side meter socket dedicated to the collar

Both ring-type and ringless meter bases may be used, depending on the socket configuration and local utility requirements.


Enphase Meter Socket Option-

For installations using a separate meter socket, Enphase offers the following:

• Model/SKU: MP-MC-200
• Type: 200 A ringless meter socket

Published enclosure dimensions:

• 15.2 inches deep
• 11.3 inches wide
• 4.5 inches high
• 200 A continuous rating


Knockout Location Information-

Enphase does not publish the bottom knockout centerline locations for the MP-MC-200 meter socket.

These dimensions are typically provided by the meter socket manufacturer in the enclosure drawing or product submittal, not in the IQ Meter Collar documentation.


Feeder Rearrangement Planning-

Before planning conduit or feeder routing:

• Select the exact meter socket model.
• Obtain the manufacturer's dimensional drawing or product submittal.
• Verify:
• Knockout sizes
• Knockout centerline locations
• Distance from the rear mounting surface
• Distance from enclosure edges

These dimensions are necessary for accurate conduit and conductor layout.


Control Wiring-

The IQ Meter Collar installation guide includes provisions for a 1/2-inch liquid-tight conduit connection for control wiring.

This conduit connection is separate from the service-conductor knockouts in the meter socket.


Utility Coordination-

Before installing the IQ Meter Collar behind the utility meter, confirm that the serving utility approves its use.

A separate load-side meter socket may eliminate the need to mount the collar on utility-owned equipment. However, utility coordination is still typically required to disconnect and restore service during installation.